System Trouble Diagnosis through System Error
Codes
When the ERR indicator of DVP-15MC series motion controller blinks or is always ON, users can get to
know the cause of an error and shoot the trouble through selecting menu Device > Diagnosis
Information... in the CANopen Builder software of version 6.0 or above.
System error code
Hexadecimal
Decimal
1000
4096
1001
4097
1002
4098
1003
4099
1004
4100
1005
4101
1007
4103
1008
4104
1009
4105
100A
4106
100B
4107
100C
4108
100D
4109
100E
4110
100F
4111
1010
4112
1011
4113
1012
4114
1013
4115
1014
4116
1015
4117
1016
4118
1017
4119
1018
4120
1019
4121
Explanation
Internal RAM detection failed
Internal Flash detection failed
The extension port detection
failed
Internal voltage is abnormal (LV)
Flash initializing failed
Flash ID detection failed.
The access to flash failed in the
Ethernet area.
The access to flash failed in the
extension area.
The access to flash failed in the
program area.
The access to flash failed in the
motion area.
The access to flash failed in the
Task area.
The access to flash failed in the
CANopen communication.
The access to flash failed in the
hardware configuration.
The access to flash failed in the
CAM area.
The access to flash (the flash
management table) failed.
The access to flash (sheet 1 in
the flash management table)
failed.
The access to flash (sheet 2 in
the flash management table) fails.
The reading of flash failed.
The writing in flash failed.
The erasing of the content in flash
failed.
CNC file ID is out of the allowed
range
The size of CNC file exceeds the
range
The
position
of
incremental
encoder 1 changes dramatically in
short time.
The
position
of
incremental
encoder 2 changes dramatically in
short time.
System stack is used up.
Chapter 12 Troubleshooting
Correction
Contact local technicians if the error still exists
after repower on.
Adjust input voltage to 24V at the power port.
Contact local technicians if the error still exists
after repower on.
Contact local technicians if the problem still
exists after re-downloading the program and
restoring the setting to the factory setting.
Check if the CNC file ID is larger than 64.
Update the software and redownload the
program if the error still exists after
redownloading the program.
CNC file is too large in size. Diminish the size
and redownload the program.
Check if the input of the encoder is too fast or
enlarge the resolution of the encoder.
Check if the input of the encoder is too fast or
enlarge the resolution of the encoder.
There are too many intermediate variables in
the program. Modify the program.
12
12-19