AddFEM
Parameter
Comment
AO8_VAL
Analog Output 8 Value
AO8_HRNG
Analog Output 8 High Range
AO8_LRNG
Analog Output 8 Low Range
AO8_SIM
Simulation Value Analog Output 8
SIMUL8
1 = Simulation on
The FEM_AO has the following output parameters:
Table 5-10
Output parameters of the FEM_AO
Parameter
Comment
QPARF
1 = Parameter Assignment Failure
QCH1_F
1 = Channel Failure AO1
QCH2_F
1 = Channel Failure AO2
QCH3_F
1 = Channel Failure AO3
QCH4_F
1 = Channel Failure AO4
QCH5_F
1 = Channel Failure AO5
QCH6_F
1 = Channel Failure AO6
QCH7_F
1 = Channel Failure AO7
QCH8_F
1 = Channel Failure AO8
5.6.3
FEM_DI – Binary Input
The following OBs must call the function block FEM_DI:
Watchdog interrupt OB for cyclic operation (for example OB 32).
Area of Application
The block outputs the binary input data of the AddFEM to its output bar.
Functional Description
The block reads the binary inputs from the AddFEM. The inputs DI5 to DI12 are
pure binary inputs. DI1 to DI3 are the pulse inputs of the counters. Input 4 is not
assigned and is therefore also not specified in the block bar. The inputs DIO1 to
DIO16 are combined inputs and outputs. They can be used both as inputs and as
outputs. Each digital input can be switched to simulation by means of a simulation
switch. If the switch SIMUDIx = 1, the simulation value DIx_SIM is output.
AddFEM
C79000–G8076–C900–03
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Commissioning / Operation / Maintenance
Data type
Visible
REAL
Yes
REAL
Yes
REAL
Yes
REAL
No
BOOL
No
Data type
Default
BOOL
0
BOOL
0
BOOL
0
BOOL
0
BOOL
0
BOOL
0
BOOL
0
BOOL
0
BOOL
0
Default
0.0
100.0
–100.0
0.0
0
5-55