Commissioning / Operation / Maintenance
Error Displays
LED
Error
type
Internal
INTF
External
EXTF
BUSF1
Bus error 1
Bus error 2
BUSF2
Redun-
RED
dancy error
Lighting
5-24
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Display
Errors determined by self monitoring:
error
RAM memory test
Check sum of correction factors
Check sum of program code flash EPROM or RAM
Process signal "Analog Out" faulty
error
Process signal "Analog In" faulty
Process signal "Digital Out" faulty
The 24 V DC load supply for the digital outputs is missing
Errors determined by self monitoring at the PROFIBUS DP
connection X3A:
Master monitoring has triggered
Sign of life has failed
Parameterization error via PROFIBUS DP connection X3A:
The received configuration message contains invalid parameter
values.
At 2–channel configuration: The received parameter values
deviate from the configuration via the PROFIBUS DP connec-
tion X3B.
Errors determined by self monitoring at the PROFIBUS DP
connection X3B
Master monitoring has triggered
Sign of life has failed
Parameterization error via PROFIBUS DP connection X3B:
The received configuration message contains invalid parameter
values.
At 2–channel configuration: The received parameter values
deviate from the configuration via the PROFIBUS DP connec-
tion X3A.
At module redundancy: The optical–fiber cable coupling between the
redundant AddFEMs has failed.
Compatibility test at the module redundancy in the LINK–UP state:
The redundant AddFEMs were configured differently
The master and the reserve modules have different firmware
version states
Flashing
AddFEM
Cause
AddFEM
C79000–G8076–C900–03