Ventilation; Cooling; Economizer (Optional); Low Ambient Cooling Operation Down To 40°F - Carrier WeatherExpert 48LC 14 Series Service And Maintenance Instructions

Single package rooftop unit with gas heat/electric cooling with puron (r-410a) refrigerant
Hide thumbs Also See for WeatherExpert 48LC 14 Series:
Table of Contents

Advertisement

Ventilation

In the Ventilation/Fan Mode (G on the thermostat), the indoor
fan will run at low speed and the damper will operate at mini-
mum position.

Cooling

In the Cooling Mode, the small and large compressors will be se-
quenced to maintain the thermostat/DDC temperature setpoint.
Table 39 shows the cooling operation based on the following
conditions.
The outdoor fan and VFD controlled indoor-fan will operate at
low, medium and high speed. The indoor-fan speed (rpm) is fac-
tory set by the CFM and static pressure requirements for the unit
installed.
Table 39 — Cooling Operation
INPUT
Compressor
Thermostat
C1
First Stage
On
Cooling (Y1)
Second Stage
Off
Cooling (Y2)
Third Stage
On
Cooling (Y3)

Economizer (Optional)

When the Economizer is in Free Cooling Mode and a demand for
cooling exists (Y1 on the thermostat), the Economizer will modu-
late the outdoor-air damper to provide a 50°F (10°C) to 55°F
(13°C) mixed-air temperature into the zone and run the indoor-fan
at high speed. As mixed-air temperature fluctuates above 55°F
(13°C) or below 50°F (10°C) dampers will be modulated (open or
close) to bring the mixed-air temperature back within control.
Upon more call for cooling (Y2 on the thermostat), the outdoor-air
damper will maintain its current position, compressor C1 will run
and the outdoor-fan will run at low speed. If there is further de-
mand for cooling, the outdoor-air damper will maintain its current
position, only compressor C2 will run and the outdoor fan will run
at medium speed. The VFD controlled indoor fan will operate at
high speed regardless of the cooling demand.
If the increase in cooling capacity causes the mixed-air tempera-
ture to drop below 45°F (7°C), the outdoor-air damper will return
to the minimum position. If the mixed-air temperature continues
to fall, the outdoor-air damper will close. Once the mixed air tem-
perature rises above 48°F (9°C), the control returns to normal. The
power exhaust fans will be energized and de-energized, if in-
stalled, as the outdoor-air damper opens and closes.
If field-installed accessory CO
omizer, a demand controlled ventilation strategy will begin to op-
erate. As the CO
level in the zone increases above the CO
2
point, the minimum position of the damper will be increased pro-
portionally. As the CO
level decreases because of the increase of
2
fresh air, the outdoor-air damper will be proportionally closed. For
48LC**
NO. OF FANS ON NO. OF FANS OFF
14
17
20
24
26
OUTPUT
Indoor
Outdoor
Compressor
Fan
C2
Speed
Speed
Off
Low
(700 rpm)
Medium
On
Medium
(800 rpm)
On
High
(1000 rpm)
sensors are connected to the econ-
2
Table 40 — Low Ambient Temperature Outdoor Fan Control
3
0
4
0
4
0
6
0
6
0
economizer operation, there must be a thermostat call for the fan
(G). If the unit is occupied and the fan is on, the damper will oper-
ate at minimum position. Otherwise, the damper will be closed.
Low Ambient Cooling Operation down to 40°F
(4°C)
In Low Ambient RTU conditions when the temperature is be-
tween 55°F (13°C) and 40°F (4°C), the Low Ambient Switch
(LAS) will be active and the outdoor-fans will run to the pre-set
factory outdoor-fan speed. When the temperature is greater than
65°F (18°C), the Low Ambient Switch will deactivate and the out-
door-fans will run in the standard cooling mode. If the Outdoor
Fan Select Switch (see Fig. 62) is in the up position, the outdoor
fans will run in the Fan Cycle Speed Mode (FCS) set to 250 rpm.
If the Outdoor Fan Select Switch is in the down position, the out-
door fans will run in the Minimum Fan Speed Mode (MIN) set to
160 rpm regardless of the cooling demand.
The 48LC 14-26 units have a SPST normally open Low Ambient
Switch wired across the TS and OF terminal and a jumper placed
across the PS terminal (See Fig. 63). When the LAS is active, the
Fan
switch will close making contact to the OF terminal. This is done
for units that require all outdoor fans to run at the same pre-set fac-
Low
tory Low Ambient Speed.
High
Fig. 62 — Outdoor Fan Speed Select Switch
Fig. 63 — Schematic of SPST Low Ambient Switch
Table 40 shows the operation of the outdoor fans for each unit.
set-
2
SWITCH
LAS Fig. No.
(1) SPST
(1) SPST
(1) SPST
(1) SPST
(1) SPST
64
OF SPEED
SELECT
ON
FCS
MIN
OFF
JUMPER ON
PS
PS
TS
OF
LAS
SPST
OF SELECT
SWITCH
63
Up
63
Up
63
Up
63
Up
63
Up
RPM
250
250
250
250
250

Advertisement

Table of Contents
loading

Table of Contents