Omron SYSMAC C200H-TC Operation Manual page 75

Table of Contents

Advertisement

C200H-TC00
Set the thermocouple type with the switch on the rear panel.
This switch is factory-set to 2 (K).
The Data Setting Console can display the range from 10%FS below the lower limit to 10%FS above the upper limit.
Input
Range
C 0 to 1,700
F 0 to 3,000
Switch
setting
C200H-TC10
Set the platinum resistance thermometer type with the switch on the rear panel.
This switch is factory-set to OFF (JPt100).
The Data Setting Console can display the range from 10%FS below the lower limit to 10%FS above the upper limit.
Input
Range
C –99.9 to 450.0
F
Switch
setting
Downloaded from
Elcodis.com
electronic components distributor
Sensor Temperature Measurement Ranges
Thermocouple
R
S
Platinum vs.
Platinum
Chromel vs.
platinum
vs.
rhodium
platinum
13%
rhodium
10%
0 to 1,700
–200 to
1,300
0 to 3,000
–300 to
2,300
0
1
2
Platinum Resistance Thermometer
JPt100
Pt100
–99.9 to 450.0
–99.9 to 800.0
–99.9 to 800.0
OFF
ON
Appendix B
K (CA)
J/L (IC)
T/U (CC)
Iron vs.
Copper vs.
alumel
constantan
constantan
–100 to
–200 to
850
400
–100 to
–300 to
1,500
700
3/8
4/9
OFF
ON
E (CRC)
B
Chromel vs.
Platinum
Nichrosil
constantan
rhodium
vs. nisil
30% vs.
platinum
rhodium 6%
0 to 600
100 to
0 to 1,300
1,800
0 to 1,100
300 to
0 to 2,300
3,200
5
6
7
N
67