Switch Settings
Removing and Attaching the Cover
Switching Memory Contents The contents of the allocated memory differ according to the Unit number set-
Setting Direction
Sensor Type
C200H-TC00j
10
Downloaded from
Elcodis.com
electronic components distributor
The switch is factory-set to OFF: Parameters can be set from the Data Setting
Console only.
The new setting is valid immediately after the switch setting is changed.
Removing the Cover
Insert a small flat-blade screw-
driver between the case and
the cover at the top of the Unit
and lever off the cover.
ting.
Normal
Data can be set as required using commands (Refer to
4-1 Memory Allocation ).
Fixed
Fixed data is allocated to memory. Direct reading and
writing of data is possible.
Refer to 4-1 Memory Allocation for details of the memory contents.
Selects whether the data settings are made from the Data Setting Console or
from the C200H PC, using a user program or Programming Console.
Executed Bank Number
The reading and setting of the executed bank number are possible from a user
program or from a device, such as the Programming Console, regardless of the
ON/OFF setting of switch SW2-2.
SW202
Sensor type setting
Setting
0
1
Sensor type
R
S
The switch is factory-set to 2.
The selected position is shown by the arrow. Turn the switch with a small flat-
blade screwdriver.
Attaching the Cover
Place the right edge of the
cover against the case and
press into position.
2
3
4
5
6
K
J
T
E
B
Selected position
Section 2-2
7
8
9
N
L
U

Advertisement