Omron SYSMAC C200H-TC Operation Manual page 26

Table of Contents

Advertisement

Wiring
Type of thermocouple
Symbol
T
Wiring Platinum Resistance
Thermometers
Current Transformer
2-3-2 Output Wiring
Connection Diagrams
C200H-TCj01 Transistor Output
C200H-TCj02/TCj03 Voltage/Current Output
Downloaded from
Elcodis.com
electronic components distributor
Compensating conductor
Previous
Symbol
symbol
(reference)
CC
TX-G
TX-GS
TX-H
TX-HS
Connect a platinum resistance thermometer with copper wire. All three leads
should have the same thickness and the same length to give them identical re-
sistances. Do not branch the two (B) leads near the terminal block as this in-
creases measurement errors.
Use an E54-CT1 or E54-CT3 Current Transformer (CT). Refer to Appendix C
Heater Burnout Detection for details of the Current Transformer specifications
and installation dimensions.
NC: Not connected
The pairs of terminals B2 to A2 and B1 to A1 are shorted internally. Always sup-
ply power to the 24-VDC terminal (B1) as this drives the internal circuits.
Classification by
Classification by
application and
application and
Previous
tolerance
tolerance
symbol
(reference)
WCC-G
General-purpose,
standard class
---
General-purpose,
precision class
WCC-H
Heat-resistant,
standard class
---
Heat-resistant,
precision class
OUT1
OUT2
24 VDC
COM
24 VDC
OUT1 (+)
OUT2 (+)
Constituent materials
+ conductor
Alloy with copper
Copper
or nickel as major
constituent
B
A
NC
NC
10
NC
9
NC
NC
NC
2
2
COM
1
1
24 VDC
B
A
NC
NC
OUT1 (–)
10
10
9
9
OUT2 (–)
NC
NC
Section 2-3
– conductor
j
tit
t
15

Advertisement

Table of Contents
loading

Table of Contents