Memory Allocation
Parameter
Alarm SV 1 (see note 4) 0
Alarm SV 2 (see note 4) 0
Input shift value
Proportional band (see
note 1)
Integral (reset) time
(see note 1)
Derivative (rate) time
(see note 1)
SP lower limit
SP upper limit
Control period (see note
1 and 3)
Hysteresis (see note 2)
Alarm hysteresis (see
note 4)
Heater current monitor
(see note 3)
Heater burnout current
(
(see note 3)
)
Control output variable
monitor
Auto-tuning start/stop
(see note 1)
Copy bank
Sensor-type monitor
Alarm 1 mode
Alarm 2 mode
42
Downloaded from
Elcodis.com
electronic components distributor
Com-
Write
Read
Loop
mand
3
Yes
Yes
Yes
4
Yes
Yes
Yes
0
5
Yes
Yes
Yes
0
6
Yes
Yes
Yes
0
7
Yes
Yes
Yes
0
8
Yes
Yes
Yes
1
0
Yes
Yes
Yes
1
1
Yes
Yes
Yes
1
7
Yes
Yes
Yes
1
8
Yes
Yes
Yes
1
9
Yes
Yes
Yes
1
A
No
Yes
Yes
1
B
Yes
Yes
Yes
2
0
No
Yes
Yes
2
1
Yes
No
Yes
2
2
Yes
No
Yes
2
3
No
Yes
Yes
2
4
Yes
Yes
Yes
2
5
Yes
Yes
Yes
Yes: Possible.
No:
Not possible or not required.
Note
1. Only when advanced PID control is selected.
2. Only when ON/OFF control is selected.
3. Does not apply to current output. A value of 5.6 (0056) for the heater current
monitor indicates that the heater current value exceeds 5.6 A.
Bank
Actual data
no.
no.
range
Yes
Alarm mode
TC 1, 4, 5:
0 to 9999 C
Other TCs:
–999 to
9999 C
9999 C
Yes
Pt 1, 4, 5:
0.0 to
999.9 C
Other Pts:
–99.9 to
999.9 C
Yes
–99.9 to
999.9 C
Yes
0.0 to
999.9 C
Yes
0 to 9999 s
Yes
0 to 9999 s
No
Sensor measuring range
lower limit to (SP upper limit
value – 1 digit)
No
(SP lower limit + 1 digit) to
sensor measuring range up-
per limit
No
1 to 99 s
Yes
0.0 to
999.9 C
No
0.0 to
999.9 C
No
0.0 to 5.6 A
No
0.0 to 5.0 A
0.0: No heater burnout
detection, alarm signal OFF
5.0: No heater burnout
detection, alarm signal ON
No
0.0% to
100.0%
No
AT start = 0001
AT stop = 0000
No
Run = 0001
No
0 to 9
No
0 to 9
Mode for Alarm SV 1/2 (0:
Mode for Alarm SV 1/2 (0:
No
no alarm)
Section 4-1
Write/Read
Default value
data range
0 C
0000 to
9999
F999 to
9999
0 C
0000 to
9999
F999 to
9999
F999 to
0.0 C
9999
0000 to
40.0 C
9999
240 s
40 s
TC: –200 C
Pt: –99.9 C
TC: 1,300 C
Pt: 450.0 C
20 s
0000 to
0.8 C
9999
0000 to
0.2 C
9999
0000 to
---
0056
0000 to
0.0 A
0050
0000 to
---
1000
---
---
Setting for
SW202
2
2

Advertisement

Table of Contents