General Specifications
Conforms to the CPU Unit specifications.
Connectable temperature
sensor (see note 1)
Current Transformer detection
current
No. of input points (loops)
Temperature control mode
Setting/Indication accuracy
(see note 2 and 3)
Hysteresis
Proportional band
Integral (reset) time
Derivative (rate) time
Control period
Sampling period
Output refresh period
Display refresh period
Input shift range
Alarm output setting range
No. of banks
Internal current consumption
External supply voltage
Dimensions (see note 4)
Weight
Note 1. Set with the switch on the rear panel. See Appendix B Sensor T emperature Measurement Range for the
measurable temperature range.
2. The set value and designated value coincide with each other.
3. The indication accuracy of thermocouples R and S at a temperature of 200 C max., that of thermocou-
ples K and T at a temperature of –100 C max, and that of thermocouple U are all 4 C, 1 digit max. The
indication accuracy of thermocouple B at a temperature of 400 C or below is not guaranteed.
4. See Appendix D Dimensions .
Downloaded from
Elcodis.com
electronic components distributor
Item
Thermocouple (R, S, K, J, T, E, B, N, L, U)
0.1 to 4.9 A (with a heater burnout detecting current difference of 0.5 A min.)
Indication accuracy: 5% FS 1 digit max.
Two points (two loops, each of which consists of a temperature sensor and a CT)
PID, ON/OFF (selectable with a switch on the rear panel)
(PID control with feed-forward circuitry with auto-tuning)
0.5% of set (designated) value or 2 C
whichever larger 1 digit max.
0.0 to 999.9 C/ F (in units of 0.1 C/ F) (during ON/OFF control action)
0.0 to 999.9 C/ F (in units of 0.1 C/ F)
0 to 9999 s (in units of 1 s)
0 to 9999 s (in units of 1 s)
1 to 99 s (in units of 1 s)
500 ms
500 ms
500 ms
–99.9 to 999.9 C/ F (in units of 0.1 C/ F)
–999 to 9,999 C/ F (in units of 1 C/ F)
8 banks
5 VDC, 0.33 A max.
+10%
24 VDC
34.5 mm (W) x 130 mm (H) x 120.5 mm (D)
360 g
Appendix A
Specifications
C200H-TC00
/
, 0.2 A min.
–15%
C200H-TC10
Platinum resistance thermometer (JPt100,
Pt100)
0.5% of set (designated) value or 1 C
whichever larger 1 digit max.
–99.9 to 999.9 C/ F (in units of 0.1 C/ F)
65