Parameter Displays and Settings
Proportional Band (Display Level 0)
Integral (Reset) Time (Display Level 0)
Derivative (Rate) Time (Display Level 0)
Downloaded from
Elcodis.com
electronic components distributor
To interrupt, press the Level and Display Keys again to display at. When at
appears, press the Up Key. On interrupt, the at display disappears and the pro-
cess value is displayed.
Auto-tuning operates only when SW203-1 on the rear panel is set to OFF to en-
able PID control with feed-forward circuitry. When auto-tuning is completed, the
AT indicator stops blinking and the P, I, and D data is written to EEPROM. If nec-
essary, the P, I, and D data can be changed as described in the following.
PV
SV
PV
SV
PV
SV
Proportional Band parameter symbol
Currently set Proportional Band. Units: C or F. The
setting can be changed from this display.
Integral time parameter symbol
Currently set integral time. Units: second. The
setting can be changed from this display.
Derivative time parameter symbol
Currently set derivative time. Units: second. The
setting can be changed from this display.
Section 3-4