Table of Contents

Advertisement

Wiring

Control Action
Control Method
2-3
Wiring
2-3-1 Input Wiring
C200H-TC00j Thermocouple
12
Downloaded from
Elcodis.com
electronic components distributor
Reverse:
For heating control with a heater. The heater output is increased when the mea-
sured temperature is below the SP (i.e., a negative temperature difference).
Normal:
For cooling control of overheated objects using cooling water or some other
method. The cooling water output is increased when the measured temperature
is above the SP (i.e., a positive temperature difference).
Selects the method of control.
CT: Current Transformer
TC: Thermocouple
Heater wire
CT
Loop 1
TC
CT
Loop 2
TC
24 VDC
0.2 A
The 24-VDC output from the
C200H CPU or the Power
Supply Units is convenient.
Terminal No.
Terminal name
A0
CT
A1
CT
A2
TC (–)
A3
TC (+)
A4
CT
A5
CT
A6
TC (–)
A7
TC (+)
A8
24 VDC
A9
0 V
A0
A1
A2
A3
A4
Refer to the
table below.
A5
A6
A7
A8
A9
Loop 1
Loop 2