Omron SYSMAC C200H-TC Operation Manual page 54

Table of Contents

Advertisement

Programming
Example 1: Write with SW2-1 Set for Normal Memory Allocations
Description and Conditions
Downloaded from
Elcodis.com
electronic components distributor
Example
The user program makes the following settings:
Loop 1 SP = 200 C (Bank no. = 1)
Loop 2 SP = 250 C (Bank no. = 2)
Loop 1 executed bank number = 1
Loop 2 executed bank number = 2
Loop 1 heater burnout current value = 2.0 A
Loop 2 heater burnout current value = 2.5 A
Conditions C200H-TC001 (thermocouple)
SW202 set to 2 (K).
Unit number set to 0 (allocated memory: IR100 to IR109).
SW2-1 set ON (Normal) and SW2-2 set ON (C200H PC).
Section 4-3