Controlling the safety functions
7.2 Control of "STO" and "SS1" via terminal module for option K82
Customer interface –X41
Table 7- 3
Terminal strip -X41
Terminal
Meaning
-X41:1
Activation –K41: A1
-X41:2
Connected to -X41:1
-X41:3
Activation –K41:A2, -K42:A2 , N conductor or ground
-X41:4
Connected to -X41:3
-X41:5
Checkback signal, status –K41, -K42
-X41:6
Checkback signal, status –K41, -K42
-X41:7
Activation –K42: A1
-X41:8
Connected to -X41:7
-X41:9
Not assigned
-X41:10
Output -K41: Permanently wired with CU320-2: -X132:4
(DI7)
Control circuit:
Rated voltage: DC/AC 24 to 230 V (0.85 to 1.1 x Us)
Max. line length (applies to total of current and return conductors):
● AC (line capacity: 300 pF/m):
● DC (min. cross-section 0.75 mm²): 1500 m
Max. connectable cross-section: 2.5 mm²
Fuse: max. 4 A
136
– 24 V: 5000 m
– 110 V: 800 m
– 230 V: 200 m
The values apply for 50 Hz, at 60 Hz the line lengths must be reduced by 20%.
WARNING
If the permissible cable lengths and/or the permissible cable capacity is exceeded,
then due to the couple capacity of the cable and the associated residual current it
may be the case that the relay remains energized in spite of opened activation
element.
Technical data
Connection for activation element at channel 1 "+"
Connection of reference potential for activation
elements at channel 1 and channel 2
Connection of supply voltage for optional
checkback signal
Connection of optional checkback signal
Connection for activation element at channel 2 "+"
Function Manual, 05/2010, A5E03264275A