Acknowledgement via PROFIsafe
The higher-level controller sets the signal "Internal Event ACK" via the PROFIsafe telegram
(STW bit 7) separately for each drive object. A falling edge in this signal sets the status
"Internal Event" in the relevant drive, which acknowledges the fault.
Faults in the drive objects (DOs) cannot be acknowledged by the higher-level controller in
the line-up but must instead be acknowledged separately for each individual drive object.
Extended acknowledgment
If STO is selected/deselected and p9307.0/p9507.0 = 1 are set, safety messages, in addition
to fault messages, are also canceled automatically.
Description of faults and alarms
Note
The faults and alarms for SINAMICS Safety Integrated functions are described in SINAMICS
Parameter Manual
Safety Integrated
Function Manual, 05/2010, A5E03264275A
Safety Integrated Extended Functions
6.11 Safety faults