Siemens SINAMICS G130 Manual page 132

Safety integrated
Hide thumbs Also See for SINAMICS G130:
Table of Contents

Advertisement

Controlling the safety functions
7.2 Control of "STO" and "SS1" via terminal module for option K82
Load side:
Operational voltage: max. 250 V DC/AC
Rated operating currents:
● AC-15 (in accordance with IEC 60947-5-1): 24 - 230 V = 3 A
● DC-13 (in accordance with IEC 60947-5-1):
Min. contact load: 5 V DC, 1 mA at 1 ppm error
Fuse: max. 4 A (fuse weld-free, duty category gL/gG with Ik ≥ 1 kA)
Figure 7-2
A switch in accordance with ISO 13850/ EN 418, positive opening in accordance with EC
60947-5-1, or a certified safety controller must be used as activation element.
132
– 24 V = 1 A
– 10 V = 0.2 A
– 230 V = 0.1 A
P
A1
-K41
A2
-X41
10
Circuit terminal module for option K82
14
12
A1
14
32
-K42
22
12
34
24
11
A2
21
11
31
1
2
3
4
7
8
5
6
EP+
32
34
22
24
21
31
9
Function Manual, 05/2010, A5E03264275A
Safety Integrated