Enclosure tamper -
and the UCM Enclosure Tamper indicator turns ON, and the Event log reports an
Enclosure Tamper alarm. If a relay is configured to activate for an enclosure
tamper, the designated Relay activates.
PASS ____
FAIL____
Self-test -
Activate the self-test for the A-side. The processor performs electronic
self-tests of the A-side. (All relays assigned to the A-Side cable should activate.)
Activate the self-test for the B-side. The processor performs electronic self-tests
of the B-side. (All relays assigned to the B-Side cable should activate.)
PASS ____
FAIL____
Auxiliary device inputs -
system self-test. In this case, activate the appropriate switch, and verify that the
self-test occurs. Repeat for both cable sides.
For Remote control mode, the Aux inputs serve as auxiliary device inputs to the
host Security Management System. In this case, activate the connected device,
and verify the status change is reported by the host SMS. Repeat for Aux 2.
PASS ____
FAIL____
Relay outputs -
For Local control mode the relay outputs are used to report
events. Cause an event, and verify that the specified relay activates for a
minimum of the relay hold time. Repeat this procedure for each specified event
(in the Output Configuration field).
For Remote control mode, the relays serve as output control points for the host
SMS. Send an activation command from the host SMS to one of the relays and
verify that the relay activates. Repeat this procedure for each relay.
PASS ____
FAIL____
Audio test -
Activate the Audio sequentially for each configured Cable, Zone, or
Cables for the connected processor. Have a tester create a disturbance on the
matching Cable, Zone, or Cables while the corresponding Audio is activated. The
fence tester and the UCM monitor must be in contact to ensure the selected
Cable, Zone, or Cables match the locations of the tests.
When the fence tester creates the disturbance, an audio signal is produced over
the PCs audio output device.
PASS ____
FAIL____
FlexZone™ Product Guide
Open the enclosure. The DOOR OPEN LED (D1) turns ON,
For Local control mode the Aux inputs activate the
Chapter 3: Calibration and setup
79