Siemens SENTRON 3WL10 Series Manual page 83

Air circuit breaker
Hide thumbs Also See for SENTRON 3WL10 Series:
Table of Contents

Advertisement

Position signaling switch PSS for guide frame
The position auxiliary contacts are used in the withdrawable breaker and signal whether the
circuit breaker is in the racking position DISCONNECT, Test, or CONNECT.
Breaker position
CONNECT: Inserted
TEST: Test position
DISCON (DISCONNECT): Removed
The position signaling switches are always installed in the guide frame. However, the user
can modify 24 V digital signals in the device configuration to meet the requirements for small
loads, e.g. for PLC connection.
Configuration
Standard contact 400 V
Contact for digital signal 24 V
Type
Smallest load
Breaking capacity
Signaling diagram of the position signaling switch PSS:
Air circuit breaker 3WL10
Manual, 11/2017, L1V30499596002-01
Auxiliary contacts
Connected
Connected
Disconnected
Changeover contact
DC
24 V
125 V
250 V
AC
250 V
400 V
3.2 Electronic accessories
Main circuit connection
Position auxiliary contacts - PSS
6 auxiliary contacts
Standard contact
Contact for digital signal
100 mA at 24 V
0.3 A at 0 ms
0.15 A at 0 ms
5 A at cosφ 1
5 A at cosφ 0.7
5 A at cosφ 0.3
3 A at cosφ 1
2 A at cosφ 0.7
1 A at cosφ 0.3
Accessories
Connected
Isolated
Isolated
Changeover contact
1 mA at 5 V
0.1 A
81