Siemens SENTRON 3WL10 Series Manual page 164

Air circuit breaker
Hide thumbs Also See for SENTRON 3WL10 Series:
Table of Contents

Advertisement

Operation
6.2 Alarms
Display of the LED ACT
The LED name "ACT" stands for ACTIVE. This LED indicates that the ETU is ready for
operation. If the LED does not light up, the power supply of the ETU is interrupted and the
ETU is not ready to operate.
ACT
Flashing slowly
(1 Hz; 0.1 s on / 0.9 s off)
Off
LED displays of the protection releases
L
S
Flashing fast
Flashing fast
(2 Hz)
(2 Hz)
Flashing slowly
Flashing fast
(0.5 Hz)
(2 Hz)
Flashing slowly
Flashing slowly
(0.5 Hz) with 2 s
(0.5 Hz) with 2 s
pause
pause
Flashing slowly
Flashing slowly
(0.5 Hz)
(0.5 Hz)
162
Alarm / status
ETU ready
ETU without power supply
I
G
Flashing fast
Flashing fast
(2 Hz)
(2 Hz)
Flashing fast
Flashing fast
(2 Hz)
(2 Hz)
Flashing slowly
Flashing slowly
(0.5 Hz) with 2 s
(0.5 Hz) with 2 s
pause
pause
Flashing slowly
Flashing slowly
(0.5 Hz)
(0.5 Hz)
Measure / comment
No measures required
Check the power supply of the
ETU via the main circuit or the
auxiliary current conductors.
Alarm / status
Measure / comment
Auxiliary solenoid
Check connections.
closing coil / shunt
release (CC/ST) not
connected or
trip command failed
Current sensor not
Check connections.
connected
Fault in rating
Check the connection
plug
between the release
and the rating plug.
Perform installation.
Internal configuration
Contact Siemens
error
Technical Support.
Manual, 11/2017, L1V30499596002-01
Air circuit breaker 3WL10

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sentron 3wl1010-2cf41-1lw1

Table of Contents