Siemens SENTRON 3WL10 Series Manual page 57

Air circuit breaker
Hide thumbs Also See for SENTRON 3WL10 Series:
Table of Contents

Advertisement

Protection functions of the ETU
N
Neutral protection
Neutral protection can be enabled/
disabled
Current setting value I
G
GF: Ground-fault protection
Protection function can be enabled/
disabled
Characteristic (switchover possible)
Setting range for operating value
I
= I
x ...
g
n
(The range <0.2 I
(for I
= 400 A) requires an external
n
auxiliary power supply of the ETU)
Setting range for delay time t
t=k
Setting range for delay time t
(reference point 2 x I
Func-
Frequency adaptation
tions
Setting of the line frequency on ETUs
of the 3-series with DIP switches
ETU powered in at least 2 phases or self-powered with auxiliary voltage. In all other cases,
1)
the following tolerances apply:
L
S
I
G
Air circuit breaker 3WL10
Manual, 11/2017, L1V30499596002-01
ETU320 LI
= I
x ...
0.5; 1; 2
N
n
Default value: 0.5
or <0.25 I
n
n
(fixed)
g
at I²t
g
)
g
50 Hz; 60 Hz
Default value: 50 Hz
Current setting value
Tripping between 1.05 and 1.2 x I
± 10 %
± 15 %
± 15 %
2.4 Electronic trip unit ETU
ETU350 LSI
0.5; 1; 2
Default value: 0.5
50 Hz; 60 Hz
Default value: 50 Hz
Tripping time
± 20 %
r
± 20 %
≤ 60 ms
± 20 %
Description
ETU360 LSIG
0.5; 1; 2
Default value: 0.5
I²t / t = constant
Default value: I²t
0.1; 0.2; 0.3; 0.4; 0.5;
0.6; 0.7; 0.8; 1
Default value: 0.1
Tolerance
: ± 7%
1)
0.1; 0.2; 0.4; 0.6; 0.8 s
Tolerance
: The better
1)
value out of ± 10 % or
± 40ms or 50 ms with
t
= instantaneous
g
0.1; 0.2; 0.4; 0.6; 0.8 s
Default value: 0.1 (I²t)
50 Hz; 60 Hz
Default value: 50 Hz
55