Siemens SENTRON 3WL10 Series Manual page 65

Air circuit breaker
Hide thumbs Also See for SENTRON 3WL10 Series:
Table of Contents

Advertisement

Alarms and functions
Alarms
Pre-alarms PAL response thresholds - function trigger
Enabling/disabling of PAL response threshold
overload current I
Enabling/disabling of PAL response threshold
overload current I
Setting range for PAL response threshold
overload current I
Setting range for PAL response threshold
overload current I
Enabling/disabling of PAL response threshold
rated current I
Enabling/disabling of PAL response threshold
rated current I
Setting range for PAL response threshold
rated current I
Setting range for PAL response threshold
overload current I
Crossing the response threshold rated
current I
n pal(1)
or from top
Crossing the response threshold rated
current I
n pal(2)
or from top
Checking the phase sequence / alarm
Checking the phase sequence can be enabled/
disabled
Setting range for phase sequence
Trip/alarm COS PHI
Trip COS PHI can be enabled/disabled
Setting range for checking the COS PHI
Functions
Frequency adaptation
Frequency adaptation for ETUs of the 3-series
with DIP switch, for ETUs of the 6-series with
menu
Nominal voltage adaptation
Nominal voltage
Only available with MF Basic or MF Advanced metering function
1)
Air circuit breaker 3WL10
Manual, 11/2017, L1V30499596002-01
r pal(1)
r pal(2)
= I
x ...
r pal(1)
r
= I
x ...
r pal(2)
r
n pal(1)
n pal(2)
= I
x ...
n pal(1)
n
= I
x ...
n pal(2)
n
Direction: from bottom,
Direction: from bottom,
1)
1)
ETU650 LSI
50 %, 100 % (in steps of 1 %)
Default value: 50 %
50 %, 100 % (in steps of 1 %)
Default value: 50 %
0.1 to 10 (in steps of 0.01)
Default value: 3
0.1 to 10 (in steps of 0.01)
Default value: 3
Default value: bottom → top
Default value: bottom → top
L1L2L3; L3L2L1
Default value: L1L2L3
0.50 to 0.95 (in steps of 0.01)
Default value: 0.95
50Hz; 60Hz
Default value: 50Hz
100 V AC to 690 V AC
Default value: 400 V AC
Description
2.4 Electronic trip unit ETU
ETU660 LSIG
50 %, 100 % (in steps of 1 %)
Default value: 50 %
50 %, 100 % (in steps of 1 %)
Default value: 50 %
0.1 to 10 (in steps of 0.01)
Default value: 3
0.1 to 10 (in steps of 0.01)
Default value: 3
Default value: bottom → top
Default value: bottom → top
L1L2L3; L3L2L1
Default value: L1L2L3
0.50 to 0.95 (in steps of 0.01)
Default value: 0.95
50Hz; 60Hz
Default value: 50Hz
100 V AC to 690 V AC
Default value: 400 V AC
63