Accessories
3.2 Electronic accessories
Remote reset magnet (RR)
With the remote reset magnet (RR), the circuit breaker can be reset remotely when the
trip unit has opened the circuit breaker.
Deliberate resetting of the ETU by mechanical operation on the device or remote resetting
via the RR is necessary for safety after overcurrent tripping. All faults in the distribution board
should be cleared first.
The reset coil is available for different voltage supplies.
Technical specifications
Rated control
supply voltage U
Operating limits
Spring charging motor (MO)
The spring charging motor (MO) automatically charges the closing springs when they are
discharged. If no power supply is available, the springs must be charged manually with the
hand lever of the operator on the circuit breaker.
Technical specifications
Rated control
supply voltage U
Operating limits (acc. to IEC 60947-2)
Switch-on power
Continuous power
Make time
Charging time
Note
The motor is always supplied with the spring charged signaling switch (S21), which signals
the state of the springs (see Section Accessories for the auxiliary and signaling switches
(Page 80)).
78
24 V
110 V
s
220 V
24 to 30 V
48 to 60 V
s
100 to 130 V
220 to 250 V
AC
•
•
•
90 to 110 % U
AC
•
•
•
•
85 to 110 % U
300 VA
100 VA
200 ms
7 s
Manual, 11/2017, L1V30499596002-01
DC
•
•
•
s
DC
•
•
•
•
s
300 W
100 W