Siemens SENTRON 3WL10 Series Manual page 165

Air circuit breaker
Hide thumbs Also See for SENTRON 3WL10 Series:
Table of Contents

Advertisement

L
S
On
Flashing fast
(2 Hz)
On
On
On
Flashing fast
(2 Hz)
Air circuit breaker 3WL10
Manual, 11/2017, L1V30499596002-01
I
G
On
Flashing fast
(2 Hz)
On
On
Alarm / status
Measure / comment
Tripping on hardware
Check the circuit
fault
breaker and
accessories.
Temperature alarm
Lower the ambient
temperature or
reduce the continuous
operating current.
Pre-alarm L, power
flow is greater than
90 % of the threshold
value
Circuit breaker has
Clear faults in the
been tripped by the
power system and
L release
close the circuit
breaker again.
Circuit breaker has
Clear faults in the
been tripped by the
power system and
S release
close the circuit
breaker again.
Circuit breaker has
Clear faults in the
been tripped by the
power system and
I release
close the circuit
breaker again.
Circuit breaker has
Clear faults in the
been tripped by the
power system and
G release
close the circuit
breaker again.
Threshold has been
Reduce rated current
exceeded, tripping
(disconnect loads)
delay is elapsing
Operation
6.2 Alarms
163

Hide quick links:

Advertisement

Table of Contents
loading