Siemens SENTRON 3WL10 Series Manual page 64

Air circuit breaker
Hide thumbs Also See for SENTRON 3WL10 Series:
Table of Contents

Advertisement

Description
2.4 Electronic trip unit ETU
Enhanced protection functions - only available with
MF Advanced metering function
V
Undervoltage protection V
u
Protection function can be enabled/disabled
Setting range of undervoltage protection
U
= U
x ...
u
n
Setting range of the delay time for undervoltage
protection
Enabling/disabling of tripping on undervoltage
protection
V
Overvoltage protection V
o
Protection function can be enabled/disabled
Setting range of overvoltage protection
U
= U
x ...
o
n
Setting range of the delay time for overvoltage
protection
Enabling/disabling of tripping on overvoltage
protection
f
Underfrequency protection f
u
Protection function can be enabled/disabled
Setting range for underfrequency protection
f
= f
x ...
u
n
Setting range of the delay time for
underfrequency protection
Enabling/disabling of tripping on
underfrequency protection
f
Overfrequency protection f
o
Protection function can be enabled/disabled
Setting range for overfrequency protection
f
= f
x ...
o
n
Setting range of the delay time for
overfrequency protection
Enabling/disabling of tripping on
overfrequency protection
PP
Reverse power protection RP
Protection function can be enabled/disabled
Setting range for reverse power PR = S
Setting range of the delay time for reverse
power protection
Definition of direction of power flow
Enabling/disabling of tripping on reverse power
62
ETU650 LSI
u
0.5 to 0.98 (in steps of 0.01)
Default value: 0.9
0.05 to 120 s (in steps of 0.01)
Default value: 10 s
o
1.02 to 1.5 (in steps of 0.01)
Default value: 1.05
0.05 to 120 s (in steps of 0.01)
Default value: 10 s
u
0.9 to 0.999 (in steps of 0.001)
Default value: 0.9
3 to 300 s (in steps of 0.01)
Default value: 3 s
o
1.001 to 1.1 (in steps of 0.001)
Default value: 1.1
3 to 300 s (in steps of 0.01)
Default value: 3 s
x ...
-0.050 ... -1.0 (in steps of
n
0.001)
Default value: -0.1
0.5 to 100 s (in steps of 0.1)
Default value: 5 s
Bottom → top; top → bottom
Default value: top → bottom
ETU660 LSIG
0.5 to 0.98 (in steps of 0.01)
Default value: 0.9
0.05 to 120 s (in steps of 0.01)
Default value: 10 s
1.02 to 1.5 (in steps of 0.01)
Default value: 1.05
0.05 to 120 s (in steps of 0.01)
Default value: 10 s
0.9 to 0.999 (in steps of 0.001)
Default value: 0.9
3 to 300 s (in steps of 0.01)
Default value: 3 s
1.001 to 1.1 (in steps of 0.001)
Default value: 1.1
3 to 300 s (in steps of 0.01)
Default value: 3 s
-0.050 ... -1.0 (in steps of
0.001)
Default value: -0.1
0.5 to 100 s (in steps of 0.1)
Default value: 5 s
Air circuit breaker 3WL10
Manual, 11/2017, L1V30499596002-01

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sentron 3wl1010-2cf41-1lw1

Table of Contents