Digital inputs/outputs
Table 6- 13
Parameter
Voltage
Typical power consumption
Signal level (including ripple)
Pins 7, 8, 10 and 11 are "rapid inputs"
Signal propagation delays for "rapid inputs"
Galvanic isolation
Voltage
Maximum load current per output
Maximum load current per connector
Note
An open input is interpreted as "low".
Only "rapid inputs" can be used as inputs for BEROs.
Terminals MEXT1 ... MEXT6 must be connected for the digital inputs/outputs to work. This
can be done as follows:
• Connect the ground reference of the digital inputs.
• A bridge to terminal M on plug connection X1.
PPU
Manual, 06/2009, 6FC5397-2DP10-0BA0
Technical data for the digital inputs/outputs of X122/X132/X142
DANGER
Notice: This removes the galvanic isolation for these digital inputs.
6.6 X122, X132 and X142 digital inputs/outputs
Values
As an input
-3 V to 30 V
10 mA at 24 V DC
High signal level: 15 V to 30 V
Low signal level: -3 V to 5 V
L → H: 10 μs
H → L: 100 μs
Reference potential is terminal MEXT1, MEXT2,
MEXT3
As an output
24 V DC
500 mA
1 A
Interfaces
51