Settings - Siemens Synco 200 SEZ220 Documentation On Basics

Signal converter
Table of Contents

Advertisement

Connection diagram
DC 0...10 V
Connection diagram
0...1000 Ω
Configuration
Setting values
Display values
Siemens
Building Technologies
Connection diagrams (examples),
An active sensor can be connected to the unit's input. Connect as follows:
G
B M G
B...
G
X... M G1
G0
G0
A passive setpoint adjuster (e.g. QAA25 or BSG21.1) can be connected to the
unit's input. Connect as follows:
G
R M
QAA25
G
X... M
G0
G0
5.3

Settings

COMMIS > CONF > INPUT X1...X5
Path:
Display
Name
LABEL
Input identifier
... > PARA > INPUT X1...X5
Path:
Display
Name
TYPE
Type
MIN VAL
Value low
MAX VAL
Value high
CORR
Correction
INFO
Path:
Display
Name
X1
X1
...
...
X5
X5
SEZ220 signal converter
Analog inputs X1...X5
continued
N
G
(2)
B1
G
X... M
G0
N1
G0
Range / comment
Assignment of TEMP, %, 0.0, 0000.
Range
NI, 2XNI, T1, PT, 0-10, OHM
−999.9...+9999.9
−999.9...+9999.9
−3.0...+3.0
Comment
Display current measured value at terminal X1.
...
Display current measured value at terminal X5.
(1)
M
BSG21.1
N1
Factory setting
NI
0
100
0 K
23 / 46
CE1P5146en
02.06.2008