Synco 200 terminal
connection concept
Note
Connection procedure
with spring cage
terminals
Steps
Siemens
Building Technologies
10
Electrical connections
10.1
Connection rules
The following illustration shows the terminal block for the SEZ220 signal converter and
its connection terminals:
Passiver Fühler/
Aktiver Fühler/
Passiver Geber
Aktiver Geber
M
M
M
X1
X2
G1 X3
X4 G1 X5
Terminal assignment
Terminal
Used for ...
Xx, M
Passive sensors and signal sources.
G1, Xx , M
Active sensors and signal sources.
Yx
Provide measured values to control devices, sequential control of
pumps, valves, fans, etc..
G und G0
AC 24 V power supply.
Only one solid or one stranded wire can be connected per terminal.
1.
1. Strip wire for 7 to 8 mm.
2. Locate wire and screwdriver size 0 or 1.
3. Push screwdriver down and, at the same time, insert the wire.
4. Remove the screwdriver.
SEZ220 signal converter
Electrical connections
Ausgangssignal
DC 0...10 V
M
M
G1
Y2
G0
G0 G0
G1
Y1
G0
G
G
2.
Systemspeisung
AC 24 V
Doppelklemme
mit interner
Verbindung
Kleinspannungsseite
Netzspannungsseite
3.
CE1P5146en
02.06.2008
35 / 46