Overview; Connections And Functions; Scope Of Delivery - Siemens Synco 200 SEZ220 Documentation On Basics

Signal converter
Table of Contents

Advertisement

Block circuit diagram
Key

Overview

Siemens
Building Technologies
2
Overview
2.1

Connections and functions

The following block circuit diagram shows the SEZ220 connections and function
blocks. The function blocks convert the signals to the inputs as per the
configuration and parameterization, and provide them via the outputs as
DC 0...10 V signals.
X1
MIN-MAX-AVR
X2
SPLIT
ENTHALPY
X3
X4
X5
Element
Explanation
X1...X5
Universal inputs for analog, passive, or active signals of various
measured values (°C, %, ---).
MIN-MAX-AVR
Function block "Min-max-average".
SPLIT
Configuration parameter. When active, the functions of MIN-
MAX-AVR are assigned to inputs X1 – X2 and X3 – X5.
ENTHALPY
Function block "Enthalpy processor".
2X-INV
Function block "Signal doubling / signal inversion".
Y1, Y2
DC 0...10 V outputs.
2.2

Scope of delivery

Standard applications, functions and connections for the SEZ220:
Subject
Canned applications
Basic type M... (MIN-MAX-AVR)
Basic type E... (ENTHALPY)
Basic type D... (2X-INV)
Function blocks
MIN-MAX-AVR (min. and max. selection, calculation of average)
ENTHALPY (calculation of enthalpy, enthalpy differential, absolute
humidity, dewpoint)
2X-INV (signal doubling, signal inversion)
Universal inputs
As analog inputs DC 0...10 V
As analog inputs Ni 1000
As analog inputs T1
As analog inputs 0....1000 Ω
As analog inputs Pt 1000
Modulating outputs DC 0...10 V
SEZ220 signal converter
Overview
SEZ220
Y1
Y2
2X-INV
Number
13
3
1
1
1
5
2
7 / 46