Siemens Synco 200 SEZ220 Documentation On Basics page 15

Signal converter
Table of Contents

Advertisement

Example
Siemens
Building Technologies
3.3.2
Menu navigation
The pictures below show menu navigation based on the following example:
Set minimum value MINVAL1 in MIN-MAX-AVR function block.
Starting point:
• Access level SERVICE
• Info level
Step
Display
1
SERVICE
INFO
PARA
2
SERVICE
PARA
3
SERVICE
PARA
4
SERVICE
PARA
5
SERVICE
PARA
SEZ220 signal converter
Operation
Procedure / results
1. Press OK:
=> The first menu item flashes, here
INFO (inputs / outputs).
Note: Text explaining the menu is
displayed together with the information
segments (here VALUES).
5146Z09
1. Press – (down) to go to menu item
PARA (S
=> PARA flashes.
2. Confirm by pressing OK.
5146Z10
Function block selection is displayed
X1 X2 X3 X4
X5
MODE
and the first function block (X1)
flashes.
5146Z11
1. Press – (down) to go to menu item
X1 X2 X3 X4
X5
MIN-MAX-AVR.
MODE
2. Confirm by pressing OK.
1
5146Z12
Parameter selection is displayed
MODE
(information segments at bottom left).
1. Press + / – to go to the desired
SET 1
parameter (MINVAL1) and then OK:
°C
=> The corresponding value
flashes.
5146Z13
2. Press + / – to select the required
value (here 0.0 °C) and confirm by
pressing OK.
=> The new value is saved.
ettings
):
15 / 46
CE1P5146en
02.06.2008