Function block MIN-MAX-AVR
6.1
Connections and functions
The following illustration displays the function block connections and selection
fields as shown on the configuration sheet:
x
x
x
x
x
MODE 1: MIN-MAX-AVR
TYP AO1
TYP AO2
MIN
MIN
MAX
MAX
AVR
AVR
Y
Y
See below for assigning connections (inputs and outputs).
The function block calculates the following based on signals received at inputs IN 1
– IN 5:
• Selection of minimum input signal (MIN)
• Selection of maximum input signal (MAX)
• Calculation of average value (AVR)
When configuration parameter SPLIT is active, the above calculations are applied
separately to these 2 ranges:
• Inputs IN 1 – IN 2
• Inputs IN 3 – IN 5
The calculations do not consider non-configured inputs.
6.2
Assign inputs
The function block is activated through the following assignments:
• At least 1 analog input Xx, and
• At least 1 of the 2 outputs Y1 or Y2.
Each analog input Xx can be assigned with a valid identifier to function block MIN-
MAX-AVR. Valid identifiers are TEMP, %, 0.0, and 0000.
When calculating the average, the first input IN 1 can be assigned more weight via
configuration parameter FACTIN1 .
Example:
Enter average value of 5 signals at input 1 and provide signals to the other 4
inputs.
Result:
The output provides the average of 9 input signals.