Error Handling - Siemens Synco 200 SEZ220 Documentation On Basics

Signal converter
Table of Contents

Advertisement

Display values
Note on MIN display
Wiring test
Note
Siemens
Building Technologies
Settings,
continued
INFO
Path:
Display
Name
MIN 1
Minimum 1
MAX 1
Maximum 1
AVR 1
Average 1
MIN 2
Minimum 2
MAX 2
Maximum 2
AVR 2
Average 2
If setting values are defined for MINVAL and MAXVAL , Yx output signal does not
necessarily correspond to the displayed minimum and maximum values.
Example:
MINVAL1 is set to 20 °C.
The assigned input signals are 12 °C, 20 °C and 60 °C.
12 °C is displayed under MIN 1.
However, output signal Y1 is DC 0 V (because MINVAL = 20 °C).
COMMIS > TEST
Path:
Display
Name
MOD1AO1
Min-max average output 1
MOD1AO2
Min-max average output 2
6.5

Error handling

A check identifies available input signals after quitting the COMMIS
(commissioning) menu. We differentiate between two cases if one of the input
signals previously acquired is missing due to short-circuit or open circuit:
Case Description
1
At least 1 input signal is
missing, but calculation is still
possible.
2
At least 1 input signal is
missing, and calculation is not
possible.
The relevant input is not monitored if one of the input signals is missing after you
quit the COMMIS (commissioning) menu.
Section 5.4 describes how to handle errors of inputs Xx.
SEZ220 signal converter
Function block MIN-MAX-AVR
Comments
Smallest value of the input signals assigned to
output Y1 (in the respective unit).
Biggest value of the input signals assigned to
output Y1 (in the respective unit).
Average value of the input signals assigned to
output Y1 (in the respective unit).
Smallest value of the input signals assigned to
output Y2 (in the respective unit).
Biggest value of the input signals assigned to
output Y2 (in the respective unit).
Average value of the input signals assigned to
output Y2 (in the respective unit).
Positions
---, 0...100 %
---, 0...100 %
Display
Fault symbol
displayed (Info pictures and INFO menu
(Inputs/outputs)).
Fault symbol
Values: MIN = 0; MAX = 0; AVR = 0.
. The calculated values are
.
27 / 46
CE1P5146en
02.06.2008