GL6000A-AU-B, GL6000D-AU-B,GL9000A-AU-B, GL9000D-AU-B, WSM
Model
Design
Frequency
Rated Output (COP)
Rated voltage
Rated amperage
Generator
Phase and wire
Power factor
Number of poles
Insulation
Voltage regulation
Total harmonic distortion
Type of coupling
Model
Design
Number of cylinders
Bore × stroke
Engine
Displacement
Engine speed
Lubricating oil
Oil capacity
Coolant capacity
Fuel
Fuel consumption (at full load)
Fuel tank capacity
Continuous operating hours
Battery (V × Ah/5Hr)
Starting system
Dimension (L × W × H)
Set
Approx net weight
Controller
Receptacles
Electrical protection
Shutdown system
*Conversion Formula: HP = 0.746 kW, PS = 0.7355 kW
GL9000A-AU-B
Salient-pole, revolving-field AC generator (AVR system with separate and self-excitation brush)
Rotor coil: Class F, Stator coil: Class B
Vertical, water-cooled, 4-cycle diesel engine
1281 mm × 618 mm × 698 mm (50.43 in. × 24.3 in. × 27.5 in.)
Analog
3 × 15A (IP56 rated, auto switched)
40A MCB (2 Pole), 16A RCBO 30mA (2 Pole) × 3, MEN link at alternator.
In case of abnormal: Oil pressure, water temperature
Emergency stop button, engine room door opened
I-14
50 Hz
8.0 kVA
8.0 kW
240 V
33.3 A
1 - 2 ϕ - W
100 %
2
5 % (No load to full load)
4 % (No load), 6 % (Full load)
Direct coupled
D722
3
ϕ 67 × 68 mm (2.6 × 2.7 in.)
0.719 L (43.9 cu.in.)
-1
3000 min
(rpm)
API service class CF or higher
3.4 L (0.90 U.S.gals)
4.1 L (1.1 U.S.gals)
Diesel fuel No. 2 (ASTM D975)
3.3 L/h (0.87 U.S.gals/h)
28 L (7.4 U.S.gals)
8.5 hrs
55B24R (12 V × 36 Ah/5Hr)
Electric
280 kg (617 lbs.)
Digital - DSE4520
Under/Over voltage and frequency
INFORMATION
GL9000D-AU-B
9Y1211607INI0013US0
KiSC issued 06, 2016 A

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Gl9000a-au-bGl9000d-au-bGl6000d-au-b