GL6000A-AU-B, GL6000D-AU-B,GL9000A-AU-B, GL9000D-AU-B, WSM
Miniature Circuit Breaker (MCB)
1. Test for continuity between the each upper and lower breaker
terminals with an ohmmeter.
2. Make sure that there is continuity when the breaker switch in
ON.
3. If there is no continuity, it indicates that the contacts are faulty.
Replace the breaker.
NOTE
• When there is a short-circuit in the wiring, the circuit
breaker trips off. If this happens, eliminate the cause, then
reset the circuit breaker. If the circuit breaker holds, test
the load for faults.
(1) Miniature Circuit Breaker (MCB)
2-S16
GENERATOR
[A] GL6000A-AU-B, GL6000D-AU-B
[B] GL9000A-AU-B, GL9000D-AU-B
9Y1211607GRS0019US0