Kubota GL6000A-AU-B Workshop Manual page 137

Diesel generator
Table of Contents

Advertisement

GL6000A-AU-B, GL6000D-AU-B,GL9000A-AU-B, GL9000D-AU-B, WSM
 Shutdown Alarm Icons
Shutdown alarms are latching and stop the generator. The alarm must be accepted and cleared, and the fault
removed to reset the module.
To clear the alarm, press the stop/reset mode
NOTE
• The alarm condition must be rectified before a reset can take place. If the alarm condition remains, it is
not possible to reset the controller.
Icon
Fault
Engine Room Door
Open
Insufficient Oil
Pressure
High Coolant
Temperature
Fail To Start
Generator Under
Voltage
Generator Over
Voltage
Generator Under
Frequency
Generator Over
Frequency
Emergency Stop
Charge Failure
button on the module.
The controller detects that engine room door is open.
The controller detects that the engine oil pressure sender has been
activated indicating insufficient oil pressure.
The controller detects that the engine coolant sender has been activated
indicating high coolant temperature.
The engine has failed to start after three start attempts.
The generator output voltage has fallen below the pre-set alarm setting.
The generator output voltage has risen above the pre-set alarm setting.
The generator output frequency has fallen below the pre-set alarm setting
after the safety on timer has expired.
The generator output frequency has risen above the pre-set alarm setting.
The emergency stop button has been depressed.
The auxiliary charge alternator voltage is low as measured from the
alternator terminal.
2-M12
Description
9Y1211607GRM0019US0
GENERATOR
KiSC issued 06, 2016 A