System Overview
1.5.10 Battery Connection (PM-9/PM-9G)
Maximum battery size 55 AH (with an external battery cabinet)
1.5.11 City Master Box Output (ILI-MB-E3 or ILI95-MB-E3)
Voltage:
Supervisory Current:
Alarm Current:
Box Trip Coil Resistance: 14.5 Ohms (max.)
Line Resistance:
Supervised against Opens and Grounds
Non Power-limited
1.5.12 Remote Signaling Output (Polarity Reversal)
(ILI-MB-E3 or ILI95-MB-E3)
Voltage:
Supervisory Current:
Alarm Current:
Line Resistance:
Supervised against Opens and Grounds
Non Power-limited
1.5.13 Releasing Service (ILI-MB-E3 or ILI95-MB-E3)
Voltage:
Supervisory Current:
Alarm Current:
Line Resistance:
Supervised against Opens and Grounds
Non Power-limited
Refer to the Compatibility Addendum to Gamewell-FCI Manuals, P/N 9000-0427, Section 3 for a
list of UL Listed, compatible releasing solenoids.
18
24 VDC (Nominal) FWR
.0018 amp
.510 amp (max.)
35 Ohms (max.)
24 VDC (nominal) FWR
.012 amp
.012 amp
2 ohms (max.)
24 VDC (Nominal) FWR
.0005 amp
.700 amp (max.)
2 Ohms (max.)
E3 Series Installation/Operation Manual — P/N 9000-0574:I 11/04/10