Digital Alarm Communicator Transmitter (DACT-E3) Connections
3.10.6 DACT-E3 Wiring Connections (Continued)
Figure 3.10.6.1 illustrates the field wiring connections for the DACT-E3.
FROM ILI-MB-E3 OR ILI95-MB-E3 TB3 PIN1
FROM ILI-MB-E3 OR ILI95-MB-E3 TB3 PIN2
RS485 COM A OUT TO NEXT DEVICE
RS485 COM B OUT TO NEXT DEVICE
FROM ILI-MB-E3 OR ILI95-MB-E3 TB3 PIN6
FROM ILI-MB-E3 OR ILI95-MB-E3 TB3 PIN7
TELCO LINE 1 TIP IN FROM STREET
TELCO LINE 1 RING IN FROM STREET
LINE 1 TIP OUT TO PREMISES PHONE(S)
LINE 1 RING OUT TO PREMISES PHONE(S)
TELCO LINE 2 TIP IN FROM STREET
TELCO LINE 2 RING IN FROM STREET
LINE 2 TIP OUT TO PREMISES PHONE(S)
LINE 2 RING OUT TO PREMISES PHONE(S)
IMPORTANT
DACT-E3 MUST BE THE FIRST
DEVICE TO THE TELCO LINES
E3 Series Installation/Operation Manual — P/N 9000-0574:I 11/04/10
LED1 LINE 1 STATUS:
OFF
ON
FLASHING = LINE 1 FAULT
LED2 LINE 2 STATUS:
OFF
ON
FLASHING = LINE 2 FAULT
LED3 STANDBY:
OFF
ON
RS485 COM A IN
RS485 COM B IN
RS485 COM A OUT
RS485 COM B OUT
24 VDC (+)
SYS NET (-)
TB1
1
TB2
Figure 3.10.6.1 DACT-E3 Wiring Diagram
E3 Series System Connections
= LINE 1 INACTIVE
= LINE 1 TRANSMITTING DATA
= LINE 2 INACTIVE
= LINE 2 TRANSMITTING DATA
= NORMAL STANDBY MODE
= TRANSMITTING OR IN TROUBLE
LED3
LED2
STANDBY LINE2
STATUS
STATUS
T1
K1
LED1
LINE1
151