PM-9/PM-9G Power Supply Connections
3.8.8 PM-9G Power Supply Wiring Connections
Table 3.8.8.1 list the field wiring connections to the PM-9G Power Supply.
Designation Description
TB1-1
TB1-2
TB1-3
TB3-1
TB3-2
TB4-1
TB4-2
TB4-3
TB4-4
TB4-5
TB4-6
JMP1
J1
JMP2
LED 2
LED 3
LED 4
NOTE 1: Must be IN (Enabled) when J1 is connected to an INI-VG Series node. Must be OUT
(Disabled) when J1 is connected to an ILI-MB-E3 or an ILI95-MB-E3 node.
NOTE 2: Connect to J1 to the INI-VG Series J4 when the PM-9 is supplying power to both the
INI-VG Series and the ILI-MB-E3 or the ILI95-MB-E3 node types. (See Note 1)
Table 3.8.8.2 lists the details for the Ground Fault supervision and settings.
Ground Fault Supervision
ILI-MB-E3/ILI95-MB-E3/ANX
INI-VGX
Only one node connected to a PM-9G (by Ribbon Cable) must have "Supervision of the PM-9G"
Enabled in CAMWorks. All additional Nodes powered from a common PM-9G must have their
Ground Fault jumpers open or disabled and the supervision of the PM-9G disabled in CAMWorks.
E3 Series Installation/Operation Manual — P/N 9000-0574:I 11/04/10
HOT/BLK
Connect to hot, 240 VAC, 50Hz/60Hz - Non Power-limited
GND/GRN Connect to ground and isolated earth ground -
Non Power-limited
NEU/WHT Connect to neutral 240 VAC, 50Hz/60Hz
BATT+
Battery positive input - Non Power-limited
BATT -
Battery negative input - Non Power-limited
24VOUT
+ 24 VDC FWR Output to AM-50 Series amplifiers,
ILI95-E3/ILI-E3 Series or ANX, TB1-2: used to power two (2)
AM-50 Series amplifiers, the ILI95-E3/ILI-E3 Series or ANX
GND
GND (-) Output to AM-50 Series amplifiers, ILI95-E3/ILI-E3
Series or ANX, TB1-1: used to power two (2), AM-50 Series
amplifiers, the ILI95-E3/ILI-E3 Series or ANX
24VOUT
+ 24 VDC FWR Output to AM-50 Series amplifiers,
ILI95-E3/ILI-E3 Series or ANX, TB1-2: used to power 2nd pair
of AM-50 Series amplifiers, ILI95-E3/ILI-E3 Series, ANX and
INI-VG Series
GND
GND (-) Output to AM-50 Series amplifiers, ILI95-E3/ILI-E3
Series or ANX: TB1-1: to second pair of AM-50 Series
amplifiers, ILI95-E3/ILI-E3 Series, ANX, and INI-VGC
24VOUT
+ 24 VDC FWR Output to other sub-assemblies:
INI-VG Series, ILI95-E3/ILI-E3 Series, or ANX
GND
Common (-) Output to INI-VG, ILI95-E3/ILI-E3 Series or ANX
IN for GND Fault Detection (See Note 1)
10-PIN Ribbon Cable Connect to the ILI95-MB-E3,
ILI-MB-E3 or ANX Connector J1, or INI-VG Series Connector
J4 (See Note 2)
Factory Use Only
Green
Lights to indicate AC power
Yellow
Lights to indicate no or low battery fault
Yellow
Lights to indicate ground fault
NOTE: AC "Brown Out" condition indicated by:
LED 2 (grn) OFF
LED 3 (yel) LIT
LED 4 (yel) LIT
Table 3.8.8.1 PM-9G Terminals, Jumpers and LEDs
Designation
Jumper Settings
W9 shorted on ILI,
JMP1 Open on PM-9G
JMP1 shorted on PM-9G,
W9 Open on ILI
Table 3.8.8.2 Ground Fault Supervision
Comments
Description
CAMWorks Settings
ILI Supervision of PM-9G
enabled.
VGX Supervision of PM-9G
enabled
E3 Series System Connections
Comments
135