2: Pm-9/Pm-9Gbattery Connections; 3: Pm-9 And Pm-9G Specifications; Pm-9/Pm-9G - Honeywell Gamewell-FCI E3 Series Installation & Operation Manual

Expandable emergency evacuation system
Hide thumbs Also See for Gamewell-FCI E3 Series:
Table of Contents

Advertisement

E3 Series System Connections
3.8.2 PM-9/PM-9GBattery Connections
Two (2), twelve volt batteries are connected in series to the PM-9/PM-9G.
See Table 3.15.1 for the Battery Calculations.
3.8.3 PM-9 and PM-9G Specifications

3.8.3.1 PM-9/PM-9G

The following list the electrical specifications for the PM-9 and PM-9G.
Specifications
Input Voltage:
Input Current:
Output Voltage:
Output Current:
Output Current:
Output Current:
Operating Temperature: 32° to 120° F (0° to 49° C)
Relative Humidity:
Supervised
Non Power-Limited
NOTE 1: Continuous standby loads in excess of .560 Amps up to 5 Amps may require a
Generator Backup or load shedding during an AC power failure. See Section 3.15 Standby
Battery Calculations in this Manual.
NOTE 2: Continuous standby loads in excess of .560 Amps up to 4 Amps may require a
Generator Backup or load shedding during an AC power failure. See Section 3.15 Standby
Battery Calculations in this Manual.
130
PM-9
120 VAC, 60 Hz
4.6 amps max. @ 120 VAC 60 Hz 2.4 amps max.
24 VDC FWR
9 amperes Alarm max. continuous 9 amperes Alarm max. continuous
5 amperes max. continuous
Standby (when the PM-9 is used
with the ILI-E3 or the ILI95-E3
Series) (See Note 1)
4 amperes max. continuous
Standby (when the PM-9 is used
with any AM-50 Series amplifier)
(See Note 2)
0 to 93%, non-condensing at 90° F
(32° C)
E3 Series Installation/Operation Manual — P/N 9000-0574:I 11/04/10
PM-9/PM-9G Power Supply Connections
PM-9G
240VAC @ 50/60 Hz
24 VDC FWR
5 amperes max. continuous Standby
(when the PM-9G is used with the
ILI-E3 or the ILI95-E3 Series)
(See Note 1)
4 amperes max. continuous Standby
(when the PM-9G is used with any
AM-50 Series amplifier)
(See Note 2)
0 to 93%, non-condensing at 90° F
(32° C)