E3 Series System Connections
3.11.5 Repeater-E3 Wiring Connections
Table 3.11.5.1 lists the field wiring connections for the RPT-E3.
Designation
Description
TB1-1
ARCNET PORT 1A
TB1-2
ARCNET PORT 1B
TB1-3
ARCNET PORT 2A
TB1-4
ARCNET PORT 2B
TB2
Earth Ground
TB3-1
COM A IN
TB3-2
COM B IN
TB3-3
COM A OUT
TB3-4
COM B OUT
TB4-1
+ 24V IN
TB4-2
Common – IN
TB4-3
+ 24 V OUT
TB4-4
Common – OUT
J10
ARCNET
U5
Fiber Port 2 IN
U7
Fiber Port 2 OUT
U4
Fiber Port 1 IN
U6
Fiber Port 1 OUT
J1
ARCNET Term
J2
GFI
J3
GND FLT
J4
Transmitter Light
Output Control
J5
Transmitter Light
Output Control
154
Broadband Network (See Note 1)
Broadband Network (See Note 1)
Broadband Network (See Note 1)
Broadband Network (See Note 1)
Local Differential ARCNET (See Note 2)
Local Differential ARCNET (See Note 3)
Local Differential ARCNET (See Note 3)
Local Differential ARCNET. Connect to NGA TB1-3. (See Note 3)
Local Differential ARCNET. Connect to NGA TB1-4. (See Note 3)
Do not use, if J10 is used.
(+24 VDC IN from TB3-6 ILI-MB-E3/ILI95-MB-E3/ANX)
(-GND IN from TB3-7 ILI-MB-E3/ILI95-MB-E3/ANX)
Do not use, if J10 is used.
Connector to ILI-MB-E3 or ILI95-MB-E3 (See Note 4)
(See Note 5)
(See Note 5)
(See Note 5)
(See Note 5)
Short when using the Local Differential ARCNET wiring to Terminal TB3. This
is the last device on the local net.
Note: If the first and last devices are SHORT, then the device between the two
must be OPEN. If the ILI-E3, ILI95-E3 Series or ANX is the first device and
the NGA is the last device, then the RPT-E3 or J1 would be OPEN.
Short to enable Ground Fault Detection on the ARCNET Network when using
copper wiring.
Short to enable Ground Fault Detection when remotely connected to a Listed
power source that does not provide earth detection.
OPEN when connected to the DC power supplied from an ILI-MB-E3,
ILI95-MB-E3, ANX, PM-9/PM-9G or INI-7100.
Comm port 1 fiber-optic transmitter drive current
Jumper contributes to drive current when SHORT.
Contributes 12.5% of maximum drive
J4, J5 & J6 OPEN - minimum drive, 12.5% of maximum.
J4, J5 & J6 SHORT - maximum drive, 100%
To match drive used on INI boards: SHORT J4, J5 and J6.
Comm port 1 fiber-optic transmitter drive current
Jumper contributes to drive current when SHORT.
Contributes 25% of maximum drive
J4, J5 & J6 OPEN - minimum drive, 12.5% of maximum.
J4, J5 & J6 SHORT - maximum drive, 100%
To match drive used on INI boards: SHORT J4, J5 and J6.
Table 3.11.5.1 Repeater-E3 Wiring Connections
E3 Series Installation/Operation Manual — P/N 9000-0574:I 11/04/10
Repeater (RPT-E3) Connections
Comments