Honeywell Gamewell-FCI E3 Series Installation & Operation Manual page 123

Expandable emergency evacuation system
Hide thumbs Also See for Gamewell-FCI E3 Series:
Table of Contents

Advertisement

E3 Series System Connections
3.7.7.1 ANX-MR-UTP Wiring Connections (Continued)
Table 3.7.7.1.2 lists the Primary and Secondary Ring Select Switch settings for the ANX-MR-UTP.
The Primary Ring Select Switch sets the network ring number for the Primary Network (uses J2,
J4, J5, and/or TB2).
The Secondary Ring Select Switch sets the network ring number for the Secondary Network (uses
TB4).
SW2 POS 1
Table 3.7.7.1.2 ANX-MR-UTP Primary and Secondary Ring Select Switch Settings
Figure 3.7.7.1.1 illustrates the SW2 switch setting for the ANX-MR-UTP.
Note 1:
The TB4-ANX UTP Network Connections use unshielded, twisted-pair 18 AWG min.
3,000 ft. (914.4m) maximum wire between the following nodes:
122
Primary Ring Select Switch
SW2 POS2
Ring 0 Node 63
0
Ring 1 Node 62 (126)
0
SW 2
SETTING SHO W N: 00010
Figure 3.7.7.1.1 ANX-MR-UTP, SW2 Switch Setting
E3 Series Installation/Operation Manual — P/N 9000-0574:I 11/04/10
Addressable Node Expander (ANX) Connections
Secondary Ring Select Switch
SW2 POS3
Ring 0 to Ring 1 Bridge
Ring 1 Node 62 (126)
0
0
1
0
1 2 3 4 5
SW2 POS4
1
Ring 0 Node 63
0
O N=1
O FF=0