E3 Series System Connections
Designation
Description
TB6-1
RS232 GND
TB6-2
RS232 TxD
TB6-3
RS232 Supervision
TB6-4
RS232 Rxd
W1, W2, W3 Factory Jumpers
W4
ARCNET Term
W5
RS-485 AUX Terminal OPEN
W7, W8
Municipal Jumpers
W9
Ground Fault Detection IN
SW2-1
Switch
SW2-2
Switch
SW2-3
Switch
SW2-4
Switch
SW2-5
Switch
J1
ILI to PM-9/PM-9G
COMM Port
J2
Local ARCNET
J5
Local ARCNET
J4
ARCNET Repeater
NOTE 1: Must be IN when connected via a ribbon cable from this ILI95-MB-E3 at J1 to a PM-9/PM-9G connector J1.
Requires the removal of the JMP-1 on the PM-9/PM-9G.
Must be OUT when a ribbon cable is not installed in J1 and the ground fault detection is being provided by an INI-VG
Series node that is being powered from a common PM-9/PM-9G.
NOTE 2: Connect J1 to PM-9/PM-9G J1 only when the PM-9/PM-9G is NOT powering an INI-VG Series sub-
assembly.
NOTE 3: Use ILI95-MB-E3 Auxiliary RS485 Port (TB3-1 COM A & TB3-2 COM B) to connect to LCD-E3 (E3
annunciator module), LCD-7100 (7100 Remote Annunciator Module), ASM-16 (Addressable Switch Module), ANU-48
(LED Annunciator Driver Module), DACT-E3 (E3 Digital Communicator Transmitter).
NOTE 4: RPT-E3 (Repeater-E3 Module) is required when this ILI-MB-E3 is networked via ARCNET to an INI-VGE,
INI-VGC, INI-VGX, or another RPT-E3 equipped node. Not required for LOCAL ARCNET communication within a
single enclosure. (J2 or J5).
NOTE 5: For Style 4, use terminals B+ & B- only. For Style 6 use terminals B+ and B- & connect return wires to A+ &
A-. For Style 7, wire as for Style 6 & use Isolator Modules and/or Isolator Detectors per recommendations as required.
NOTE 6: NAC1 and NAC2 are rated as Special Application.
NOTE 7: When used for Releasing, must be configured in CAMWorks for Releasing in the General Settings Section.
Table 3.2.1.1 ILI-MB-E3 Field Wiring Connections (Continued)
NOTE: For additional information on the wiring requirements, refer to the ILI-MB-E3 Installation
Instructions, P/N 9000-0579.
100
To red lead on download cable P/N 75267
To black lead on download cable P/N 75267
Optional Printer Supervision
To green lead on download cable P/N 75267
Factory User Only (Default OUT)
OPEN
= Normal Operations
SHORT = If the ILI-MB-E3 is located at the end of the ARCNET bus.
= OFF (Normal Operations)
SHORT = ON (RS-485 Termination
= For Master Box or Releasing
= ENABLE
OUT
= DISABLE (See Note 1)
1 ON
= SLC 1 DISABLED
(OFF
= SLC 1 ENABLED)
2 ON
= SLC 2 DISABLED
(OFF
= SLC 2 ENABLED)
3 ON
= NAC 1 & 2 DISABLED
(OFF
= NAC 1 & 2 ENABLED)
4 ON
= BUZZER DISABLED
(OFF
= BUZZER ENABLED)
5 ON
= RS-232 115.2 K BAUD
(OFF
= defined by CAMWorks™)
Connects to PM-9/PM-9G J1(See Note 1 & 2)
Connects to J5 of the next ILI-E3, ILI95-E3 Series or ANX sub-assembly
Connects to J2 from the previous ILI-E3, ILI95-E3 Series or ANX
sub-assembly
Connects to INI-VG J7 or J10 of the RPT-E3. (See Note 4)
E3 Series Installation/Operation Manual — P/N 9000-0574:I 11/04/10
Intelligent Loop Interface-Main Board Connections
Comments