Digital Alarm Communicator Transmitter (DACT-E3) Connections

3.10.5.1 Reporting Codes for Non-SLC-Device Events

For events that do not originate on SLC devices, the DACT-E3 reports extended codes in the range
900-999. These codes are not user-configurable. Figure 3.10.5.1.1 lists the extended codes.
Code
000
Phone Line Test
001 - 899
SLC Device Codes
900
Reserved
901
SLC 1
902
SLC 2
903
NAC 1
904
NAC 2
905
Municipal Circuit
906
Aux Power Fault
907
Municipal Circuit Supervision
908
Positive Ground Fault
909
Negative Ground Fault
910
RS-232 Supervision Fault
911
Annunciator Fault
912
PM-9/PM-9G Supervision
Fault
913
Battery Low
914
Battery Fault
915
AC Fault
916
DC Fault
917
Reserved
918
Battery Charger Fault
919 - 924
Reserved
925
DACT Account 1 Fault
926
DACT Missing
927
DACT Report Timeout
928
DACT Account 2 Fault
929
DACT Line 1 Fault
930
DACT Line 2 Fault
931
INI Communication Fault
932
INI Node Number Fault
933
Net Port 1
934
Net Port 2
935 - 950
Reserved
951 - 981
Cross Zone 1 - 31
982
Node Missing Faults
983
Node Extra Faults
984
LCD Display Faults
985
ASM/ANU Faults
986
External Faults
987 - 999
Reserved
991
Test with Exception
992 - 999
Reserved
Table 3.10.5.1.1
E3 Series Installation/Operation Manual — P/N 9000-0574:I 11/04/10
Event
Automatic DACT test OK.
User-defined in device configuration
Loop Break, Short, or Disconnect
Loop Break, Short, or Disconnect
Fault, Short, or Disconnect
Fault, Short, or Disconnect
Master Box Trouble
Resettable or Non-Resettable B+ Fault
Issued if node address DIP switches do not match the node number
in the node's configuration.
Cross Zone 31 (981) is used to report Group Cross Zone Events.
Node not reported
Node not reported, reports only when Extra Node enabled
Address not reported
Address not reported
e.g. INI-VG troubles that have no ILI equivalent
Automatic DACT test OK, but Trouble condition present in the system.
Non-SLC Device Events Reporting Codes
E3 Series System Connections
Comment