Power-Limited – Non Power-Limited Wiring

8.1 E3 Series Control Panel Circuit Wiring Requirements

Table 8.1.1 provides the circuit wiring requirements for the E3 Series control panel.
Circuit Type Circuit Function
SLC
Connects to
(power-limited)
intelligent and
addressable
modules.
Or
EIA-485
Connects to
(power-limited)
LCD-E3, ASM-16,
and ANU-48
modules
EIA-232
Connects to
(power-limited)
Printers, CRT,
E3 or PC.
NAC
E3
Notification
(power-limited)
Appliance
Circuit
24 VDC Power
To Transmitter
Runs
Annunciator
(power-limited)
CHG-120
External battery
charger
ARCNET
Provides interface
(power-limited)
between network
nodes.
ARCNET should
be installed in a
separate conduit.
Note: Lightning arresters required on circuits extending between buildings; 999 meter length maximum to meet UL
1459.
Table 8.1.1 E3 Series Control Panel Wiring Requirements
182
Wire Requirements
Twisted-unshielded pair, 12 to 18 AWG
2
(3.1 to 0.78 mm
) 40 Ohms maximum
per length of Style 6 & 7 loops. 40
Ohms combined-branch circuits
maximum for Style 4 loop.
MC cable with 2 conductor twisted.
Shielded wire, in conduit or outside of
conduit or MC cable.
MC cable with 3 conductor twisted.
Note: Maximum total capacitance of all
SLC wiring (both between conductors
and from any conductor to ground)
should not exceed 0.5 microfarads.
Twisted-unshielded pair with a
characteristic impedance of 120
2
Ohms. 18 AWG (0.78 mm
Twisted-unshielded pair. 18 AWG
2
(0.78 mm
) minimum
12-18 AWG (3.1 to 0.78 mm
alarm current level, no more than a 1.2
V drop at the end of the circuit, or sized
to provide the minimum rated
operating voltage of the appliances
used.
12-18 AWG (3.1 to 0.78 mm
wire so that no more than 1.2 V drop
across wire run from supply source to
end of any branch.
2
12 AWG (3.1 mm
) in conduit
Twisted-unshielded pair, low
capacitance 18 AWG
E3 Series Installation/Operation Manual — P/N 9000-0574:I 11/04/10
E3 Series Control Panel Circuit Wiring Requirements
Distance
(feet/meters)
10,000 ft. (3,000 m)
8,000 ft. (2,400 m)
4,875 ft. (1,450 m)
3,225 ft. (980 m)
1,000 ft. (304.8 m)
3,000 ft .(maximum)
) minimum.
50/15.24
(without modem)
2
). At
To meet 1.2 V drop, or
sized to provide the
minimum rated
operating voltage of
the appliances used.
2
). Size
To meet 1.2 volt drop 12 to 18 AWG
20/6.1 (maximum)
3,000 ft. (.914 m)
Typical Wire Type*
2
12 AWG (3.1 mm
)
2
14 AWG (2.00 mm
)
2
16 AWG (1.30 mm
)
2
18 AWG (0.78 mm
)
12 to 18 AWG
2
(3.1 to 0.78 mm
)
2
16 AWG (1.30 mm
)
2
16 AWG (1.30 mm
)
12 to 18 AWG
2
(3.1 to 0.78 mm
)
2
(3.1 to 0.78 mm
)
2
12 AWG (3.1 mm
)
2
18 AWG (3.1 mm
)