E3 Series System Connections
3.7.3 ANX Wiring Requirements
Table 3.7.3.1 lists the wiring requirements for the ANX-SR, ANX-MR-FO and ANX-MR-UTP
sub-assemblies.
Circuit Type
Circuit Function Wire Requirements
EIA-232
Connects to Printers,
(power-limited)
CRT, or PC.
ARCNET
Provides the interface
(power-limited)
between network
nodes. ARCNET
should be installed in
a separate conduit.
Ethernet
Data Communications CAT5
(See Note 2)
NOTE 1: The lightning arresters are required on circuits extending between buildings; 999 meter length maximum
to meet UL 1459.
NOTE 2: The PNET1GB Ethernet circuit protector is required for permanent connections (for example, FocalPoint).
3.7.4 FocalPoint Gateway-3 Wiring
The FocalPoint Gateway panel wiring information and diagrams are included in the FocalPoint
Gateway-3 Installation & Operation Manual. For information on the wiring and operation of the
FocalPoint Gateway-3 panel, refer to the FocalPoint Gateway-3 Installation & Operation Manual,
P/N 53553.
3.7.5 License

3.7.5.1 From uIP

uIP
is an open source software, licensed under the following BSD-style license:
Copyright (c) 2001-2006, Adam Dunkels and the Swedish Institute of Computer Science All rights
reserved.
NOTE: SOFTWARE WARRANTY DISCLAIMER
THIS SOFTWARE IS PROVIDED BY THE AUTHOR 'AS IS' AND ANY EXPRESS OR IMPLIED
WARRANTIES,
MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE ARE DISCLAIMED. IN NO EVENT
SHALL THE AUTHOR BE LIABLE FOR ANY DIRECT, INDIRECT, INCIDENTAL, SPECIAL, EXEMPLARY,
OR CONSEQUENTIAL DAMAGES (INCLUDING, BUT NOT LIMITED TO, PROCUREMENT OF
SUBSTITUTE GOODS OR SERVICES; LOSS OF USE, DATA, OR PROFITS; OR BUSINESS
INTERRUPTION). HOWEVER, CAUSED AND ON ANY THEORY OF LIABILITY, WHETHER IN
CONTRACT, STRICT LIABILITY, OR TORT (INCLUDING NEGLIGENCE OR OTHERWISE) ARISING IN
ANY WAY OUT OF THE USE OF THIS SOFTWARE, EVEN IF ADVISED OF THE POSSIBILITY OF
SUCH DAMAGE.
116
Twisted-unshielded
pair. 18 AWG
(0.78 mm
Twisted-unshielded
pair low capacitance
18 AWG
(Crossover or Straight-
through)
Table 3.7.3.1 ANX Wiring Requirements
INCLUDING,
BUT
NOT
E3 Series Installation/Operation Manual — P/N 9000-0574:I 11/04/10
Addressable Node Expander (ANX) Connections
Distance
50/15.24
(without modem)
2
) minimum
3,000 ft. (.914 m)
300 ft. (100 m)
(10/100 Ethernet)