Mod "A" Solid State Starter Screen; Figure 34 - Mod "A" Solid State Starter Screen - York YK-EP B Operation & Maintenance Manual

With optiview control center solid state starter and variable speed drive
Table of Contents

Advertisement

FORM 160.87-OM1
ISSUE DATE: 8/24/2018

MOD "A" SOLID STATE STARTER SCREEN

FIGURE 34 - MOD "A" SOLID STATE STARTER SCREEN

OVERVIEW
This screen displays all information pertaining to the
Mod "A" Solid State Starter.
DISPLAY ONLY
Motor Run (LED)
Indicates whether the digital output from the controls is
commanding the motor to RUN.
Motor Heater (LED)
Indicates whether the optional Motor Heater is ON or
OFF.
Motor Current % Full Load Amps
Displays the motor current as a percentage of the Full
Load Amps (FLA) value. This is the data returned by
the Starter Logic Board for the Solid State Starter.
Current Limit Setpoint
Displays the current limit value in use. This value could
come from a 0 to 20mA, 4 to 20mA, 0 to 10VDC or 2
to 10VDC input in Analog Remote mode, PWM signal
in Digital Remote mode, E-Link Gateway interface in
ISN mode, or a locally programmed value.
JOHNSON CONTROLS
SECTION 2 - OPTIVIEW CONTROL CENTER INTRODUCTION
Pulldown Demand Time Left
Displays the time remaining in the programmed
pulldown period if the value is nonzero.
Scale/Model
Display information about the Liquid Cooled Solid
State Starter Rating and the maximum allowed Full
Load Amps.
Voltage – Phase A, B, C
Display the 3-phase input line voltage values being
read from the Solid State Starter.
Current – Phase A, B, C
Display the 3-phase motor current values being read
from the Solid State Starter.
PROGRAMMABLE
Local Motor Current Limit
Access Level Required: OPERATOR
Allows the user to specify the maximum allowed mo-
tor current (as a percentage of FLA). When the mo-
tor current reaches this value, the Pre-Rotation Vanes
LD22048
83
2