SECTION 2 - OPTIVIEW CONTROL CENTER INTRODUCTION
Pulldown Demand Limit
Access Level Required: OPERATOR
Allows the user to specify the current limit value (as
a percentage of Full Load Amps) to which the chiller
will be limited during the specified pulldown limit
time. Adjustable from 30% to 100%, Default = 100%.
This value will override the Motor Current Limit value
during this time period. This function is used to pro-
vide energy savings following chiller start-up.
Pulldown Demand Time
Access Level Required: OPERATOR
Allows the user to set a period of time for which the
pulldown demand limit will be in effect after the chiller
starts.
Print
Access Level Required: VIEW
Generates setpoints print report.
118
NAVIGATION
Home
Access Level Required: VIEW
Returns user to HOME Screen.
Setup
Access Level Required: VIEW
Moves to the subscreen allowing setup of general sys-
tem parameters.
Quick Start
Access Level Required:
ADMIN (to initially enable the feature);
SERVICE (if feature is enabled)
Moves to the subscreen allowing the Quick Start fea-
ture to be enabled/disabled. Once enabled, this screen
allows programming and viewing of Quick Start
setpoints and parameters. This feature is only available
on LVVSD and MVVSD.
FORM 160.87-OM1