York YK-EP B Operation & Maintenance Manual page 80

With optiview control center solid state starter and variable speed drive
Table of Contents

Advertisement

SECTION 2 - OPTIVIEW CONTROL CENTER INTRODUCTION
Voltage Range
Access Level Required: SERVICE
Allows the user to select specific line voltage range for
voltage checking. When not disabled, this line voltage
range is used to determine a low line and high line volt-
age threshold for initiating a shutdown.
Starting Current
Access Level Required: SERVICE
Defines the maximum allowed motor starting amps.
The Solid State Starter will limit the motor Starting
Current to this value.
KWH Reset
Access Level Required: ADMIN
Allows the user to reset the cumulative kilowatt hours.
Open SCR (Enabled/Disabled)
Access Level Required: SERVICE
Allows the user to enable or disable the Solid State
Starter Open SCR safety detection. This must never be
disabled unless under advisement of the Johnson Con-
trols Factory.
Shorted SCR (Enabled/Disabled)
Access Level Required: SERVICE
Allows the user to enable or disable the Solid State
Starter Shorted SCR safety detection. This must never
be disabled unless authorized by Johnson Controls.
80
NAVIGATION
Home
Access Level Required: VIEW
Returns user to HOME Screen.
Motor Details
Access Level Required: SERVICE
Moves to a subscreen that provides information and
setpoints pertinent to the Motor Monitoring feature if
the Motor Monitoring option is installed.
Motor Lube
Access Level Required: VIEW
Moves to the subscreen allowing operator acknowl-
edgement of the compressor motor lubrication and
viewing of the compressor motor lubrication param-
eters.
Economizer Compressor
Access Level Required: VIEW
Jumps to the Economizer Compressor screen.