SECTION 2 - OPTIVIEW CONTROL CENTER INTRODUCTION
Condenser Pressure
Displays the refrigerant pressure in the condenser.
Condenser Saturation Temperature
Displays the saturation temperature in the condenser.
Oil Sump Temperature
Displays the temperature of the oil in the sump.
Oil Pressure
Displays the pressure differential between the high side
oil pressure transducer (output of oil filter) and the low
side oil pressure transducer (compressor housing). The
displayed value includes offset pressure derived from
auto-zeroing during the System Prelube. If either of the
transducers used to calculate this differential is out of
range, the display field will show XX.X.
26
PROGRAMMABLE
None
NAVIGATION
Home
Access Level Required: VIEW
Returns user to HOME Screen.
Economizer System
Access Level Required: VIEW
Navigates to a screen displaying the Economizer Sys-
tem parameters.
FORM 160.87-OM1
ISSUE DATE: 8/24/2018