Motor Starter Screen - York YD Mod D Operation Manual

Table of Contents

Advertisement

Motor starter screen

Figure 27: Motor starter screen
This screen displays information on the motor starter.
Table 64: Display only fields
Field/LED name
Lead compressor
Motor run (LED)
% Full Load Amps
Motor current limit setpoint
Operating hours
Number of starts
Motor heater (LED)
Table 65: Programmable
Button
Access level
Local chiller
Operator
current limit
Lead compressor
pulldown
Operator
demand limit
Lead compressor
Operator
pulldown time
76
Description
Displays whether compressor 1 or compressor 2 is the lead compressor.
Separate indication showing whether the digital output from the controls is
commanding motor 1 or motor 2 to RUN.
Displays the motor current as a percentage of the Full Load Amps (FLA) value for
motor 1 and motor 2.
Displays the current limit value in use. This value could come from a 0 to 20 mA, 4
to 20 mA, 0 to 10 VDC or 2 to 10 VDC input in Analog Remote mode, PWM signal in
Digital Remote mode, SC-EQ communications interface in ISN (BAS) mode, or a locally
programmed value.
Individually indicates the total number of hours compressor 1 and compressor 2 have
run.
Individually indicates the total number of times compressor 1 and compressor 2 have
started.
Indicates whether the digital output from the controls is commanding the optional
motor heater on for each motor. This LED is not displayed if the option is not installed.
Description
Sets the maximum current draw of the chiller when run in the Local Mode. This is
the total current of motor 1 and motor 2 added together. Adjustable between 30 and
100%, default = 100%.
Sets the maximum current draw of the lead compressor during initial start for the
selected Pulldown Time. Adjustable between 30 and 100%, Default = 100%.
Sets the amount of time that the lead compressor pulldown demand limit setpoint will
be in effect. Adjustable between 0 and 255 minutes, Default = 0 minutes.
Model YD Mod D with OptiView Control Center

Advertisement

Table of Contents
loading

Table of Contents