SECTION 2 - OPTIVIEW CONTROL CENTER INTRODUCTION
FIGURE 60 - SECURITY LOG SCREEN
OVERVIEW
This screen displays a listing of the last 75 setpoint
changes. They are listed and numbered in reverse or-
der in which they were changed, with the most recent
listed as number 1. Multiple pages are necessary to dis-
play all 75 changes. Not all setpoints are logged.
The details of any setpoint change can be viewed by
navigating to a subscreen that displays the date and
time of the change, access level and User ID used to
make the change, the old setpoint value and the new
setpoint value.
Requires a login access level of SERVICE.
DISPLAY ONLY
Category
Displays the category of the setpoint (motor, evapora-
tor, condenser, etc.).
142
SECURITY LOG SCREEN
Setpoint
Displays the setpoint that was changed.
New Value
Displays the value that was entered at the time of the
setpoint change.
PROGRAMMABLE
Log Entry
Allows the user to select a particular setpoint change
for detail viewing.
Print
Generates a detailed report of all setpoint changes list-
ed in the setpoint change log.
Page Up
Scroll up in the displayed data (if applicable).
Page Down
Scroll down in the displayed data (if applicable).
FORM 160.87-OM1
ISSUE DATE: 8/24/2018
00662VIP
JOHNSON CONTROLS