York YK-EP B Operation & Maintenance Manual page 86

With optiview control center solid state starter and variable speed drive
Table of Contents

Advertisement

SECTION 2 - OPTIVIEW CONTROL CENTER INTRODUCTION
Temperature – Phase A, B, C
Displays the temperatures of the Silicon Controlled
Rectifier assemblies.
PROGRAMMABLE
Full Load Amps
Access Level Required: SERVICE
Defines the maximum amps at which the motor can oper-
ate. This value is viewable when logged in at OPERATOR
or VIEW access level.
Voltage Range
Access Level Required: SERVICE
Allows the user to select specific line voltage range for
voltage checking. When not disabled, this line voltage
range is used to determine a low line and high line volt-
age threshold for initiating a shutdown.
Starting Current
Access Level Required: SERVICE
Defines the maximum allowed motor starting amps. The
Solid State Starter will limit the motor starting current to
this value.
Open SCR (Enabled/Disabled)
Access Level Required: SERVICE
Allows the user to enable or disable the Solid State
Starter Open SCR safety detection. This must never
be disabled unless under advisement of the YORK
Factory.
Shorted SCR (Enabled/Disabled)
Access Level Required: SERVICE
Allows the user to enable or disable the Solid State
Starter Shorted SCR safety detection. This must
never be disabled authorized by a Johnson Controls
Representative.
86
KWH Reset
Access Level Required: SERVICE
Moves to a screen to allow a service technican to reset
the KWH.
Motor Details
Access Level Required: SERVICE
Moves to a subscreen that provides information and
setpoints pertinent to the Motor Monitoring feature.
Only displayed if this option is installed.
Motor Lube
Access Level Required: VIEW
Moves to the subscreen allowing operator acknowl-
edge-ment of the compressor motor lubrication and
viewing of the compressor motor lubrication param-
eters. Only displayed if this option is installed.
NAVIGATION
Home
Access Level Required: VIEW
Returns user to HOME Screen.
Economizer Compressor
Access Level Required: SERVICE
Moves to a screen displaying the Economizer Com-
pressor information.
FORM 160.87-OM1
ISSUE DATE: 8/24/2018
JOHNSON CONTROLS

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents